  160GF diesel generator technical specifications as follows: 

model

160GF

Generator rated poweKw/kva

160/200

 rated current A

288A

Standby powerKw/kva

176/220

Engine model

steyr diesel engine

Cylinder NO.

6

Type

Four-stroke, water-cooled, in-line,direct injecting wet cylinder liner1500RMP

Engine rated power

170KW

Air intake mode

turbocharged

Bore/stroke(mm)

126*130

Mechanical governor rate

≤5%

Electronical governor rate

≤1%

Noise leveldb(A)

≤108

Lube oil capacity

19L

Rated Fuel consumptionL/h

43.3

Power Alternator ratedKw/kva

160/200

Power efficiency

93.30%

Voltage regulation

≤±1.5

Excitation type

Brushless

insulation

H

measurement (mm)

2800×1000×1540

Gross weight(kg)

2550

 1) Output range: from 150kW (187.5kVA) up to 200kW (250kVA)
2) Engine model: WD615.64D, WD615.68D, WD618.42D
3) Alternator model: GM / MP
4) Water-cooled
5) 8hrs operation base tank
6) Key start / auto start
7) Sound-proof / weather-proof canopy is optional
8) 230 / 400V AC, 50Hz / 60Hz, 0.8pF three-phase and four wires
alternating current output
9) Frequency: <3%
10) Frequency at stable state: <0.5%
11) Frequency deviation at instantaneous state: ≤+10%
12) Frequency return time: ≤3s
13) Voltage deviation at stable state: ≤±1%
14) Voltage deviation at instantaneous state: ≤+20%
15) Voltage return time: ≤4s
16) Voltage modulation: ≤0.3%
17) Standard configuration of gensets:
a) Engine: Steyr diesel engine
b) Engine type: water-cooled, in line four-stoke, Humit cylinder liner,
direct injection
18) Alternator: Marathon brushless alternator
18) Control system:
a) Automatic alarm system: the unit has the acousto-optics alarm
system and arrestor for any situation as the start defeat, the water
is over temperature, the oil pulls down, over speed, over load and
over current
b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers
19) Starting system: DC alternator is used to start engine
20) Short circuit protection: MCCB air switch
21) Cooling system: combined cooling water tank fitted to meet the
requirement of radiation at ambient temperature 40°C
22) Filter system: oil, fuel and air filter
23) Accessories: exhaust elbow, bellow, muffler
24) Supply standard collocation:
a) Diesel engine with all accessories, 3 filter, electric systems
b) Alternator
c) Steel structure
d) Fan and water tank cooling system
e) Flange connector
f) 12 / 24V starting motor and charge engine
g) Air cleaner, fuel cleaner, oil cleaner
h) On-board control panel
i) MCCB air conservation switch
j) 12 / 24V starting accumulator and battery line
k) Set shock absorber
l) High-efficient silencer


Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.